Model PDP Series 200 maxDPU4E Hardware Guide
second and state changes are time stamped with 1 ms resolution and stored in
the DPU's 10,000-event buffer. Each input has a separately configurable
digital filter for contact debounce.
Distributed Processing Unit Specifications
Operating temperature range
0 to 60 degrees C
Storage temperature range
(-)25 to 70 degrees C
Relative humidity range
5 to 90% noncondensing
Power requirements
24 VDC ±4 VDC
Current:
1.2 A @ 24 VDC
Powering the DPU
The DPU operates from the main redundant 24 VDC power supply system in
the maxDNA system cabinets.
Onboard DC/DC regulators provide 5 V and 3.3 V power for the card.
Mounting the DPU
The DPU is mounted on the Input/Output (I/O) backpanel with maxPAC and
earlier Model 564 Input/Output modules.
Positioning the DPU
The DPU must be mounted in the right most position of the Model IOP rack
since the DPU is wider than the I/O cards and requires good airflow. In a six-
wide or 8-wide maxPAC I/O rack, the mounting bracket to the left of the
DPU must be removed since the DPU requires a DPU chassis to be mounted
in this slot location.
When using a second DPU for backup, it should be mounted vertically
beneath the primary DPU for ease of connection of the two-foot backup
cable.
When the DPU is installed in the right most slot of a six-wide backpanel, the
DPU cover extends over the connectors on the backpanel. The standard I/O
Backpanel daisy-chain cable (064353) must be used since it uses a low
profile connector that prevents any interference between the DPU cover and
the cable connector.
Any cables higher than 1 inch above the surface of the backpanel, and any
terminators, will interfere with the cover. Some older cables, in particular,
Metso Automation MAX Controls Inc. • 278590 •