Model PDP Series 200 maxDPU4E Hardware Guide
Serial port 1 is a nine pin RS-232C port that is used to update the DPU BIOS
and firmware, if necessary.
Serial port 2 is a twenty-five-pin serial port that supports multiple interface
standards. This port will be used by the DPU to interface with external PLC
type equipment.
maxNET Interface Ports
Dual Ethernet 10Base-T ports are provided to interface with the maxNET
communication network. These ports run at 10Mbps, full-duplex.
Backup Port
A 100Mbps Ethernet interface is provided to pass database information to a
hot standby DPU. A custom Category 5 Ethernet cable (Part 089424) is used
to connect both DPUs via this port. A status signal is also passed between
DPUs through this port to indicate which DPU is in control.
Three Rotary Address Switches
Three rotary switches set a unique IP address extension for the DPU. The
DPU network A IP address is 172.16.x.y where x is read from the high
network switch while y is the combination of the middle and low network
switches. The network B IP address is 172.17.x.y. See Chapter 3, "DPU
Switch Settings and Button Controls," for a discussion of these switches.
Mode Switch
The Mode Switch is a 16 position rotary switch. The DPU reads the switch
during a reset or power up cycle in order to determine the desired operational
mode.
Key Switch
The Key Switch requires a key to change the operating mode of the DPU
from Off-line (monitor inputs but do not change any outputs) to Run (normal
operation) to Locked (normal operation but the DPU will not accept a full
database download).
Metso Automation MAX Controls Inc. • 278590 •
1-6