Model PDP Series 200 maxDPU4E Hardware Guide
It is also possible for the DPU to automatically clear its database. When the
DPU starts up, it reads its IP address from the switches on the chassis panel.
If the DPU has a database, it compares the switch address with the address in
its database. If they are different, the DPU will clear its database. This is a
safety measure that is intended to prevent incorrect control operation that
might otherwise be caused by installing a loaded DPU in the wrong chassis.
Starting a Standalone DPU
Perform the following steps to ensure that a DPU is completely configured
before it is allowed to assume control. It is important that the DPU not be
placed in the Online state until it has been fully configured.
To start a standalone DPU:
1. Turn the DPU key switch to the Off-line position (fully
counter-clockwise).
2. Set the front panel mode switch to “B” to demand a Cold startup, as
described in the preceding section if necessary.
3. Verify that the NiCd battery pack is plugged in to connector J13 on the
DPU (refer to the chapter on battery and fuse maintenance).
4. Verify the proper IP Address is set in the Network Address switches.
5. Position the DPU into the top and bottom card guides of the chassis but
do not push it in all of the way.
6. Carefully slide the module forward, verifying that the connector pins on
the solder side of the module engage the corresponding contact guides on
the chassis assembly.
7. When the contacts are engaged and resistance is felt, firmly press on the
front panel of the DPU’s front plate to make the simultaneous
connections at the front and rear. Apply pressure to the left of the LEDs
to place the force directly in line with the printed circuit card of the
module.
8. Secure the module to the chassis assembly with the top and bottom lock
down screws on the front of the module.
9. It will take up to about a minute for a blank DPU to boot (if a DPU has a
large database, the boot time can be up to about 2 minutes).
10. Return the Mode switch to “F.”
11. Verify that the battery test passes (Battery LED is green.). This can
take up to about another minute.
Metso Automation MAX Controls Inc. • 278590 •
7-2
Comentários a estes Manuais